TeSys GV electrical trip, MN undervoltage release, 380-400V AC 50Hz / 440V AC 60Hz, for motor circuit breakers GV2ME used in safety-related systems. It trips the circuit breaker when the control voltage drops below 0.35 Uc, possible opening between 0.35-0.7 Uc. Closing of the circuit breaker is only possible when the control voltage is applied in the range 0.85-1.1 Uc. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC, INRS, VDE 0113), Green Premium compliant (RoHS/REACh).
Main
- Range:
- Product or component type: Safety undervoltage trip
- Device short name: GVAX
Complementary
- Range compatibility:
- Control circuit voltage ([Uc]):
- 380...400 V AC 50 Hz
- 440 V AC 60 Hz
- Control circuit voltage limits:
- Rated insulation voltage ([Ui]):
- 690 V AC (conforming to IEC 60947-1)
- 600 V AC (conforming to UL 60947-4-1)
- 600 V AC (conforming to CSA C22.2 No 60947-4-1)
- Threshold tripping voltage:
- Inrush power:
- Hold-in power consumption:
- Operating time:
- 10...15 ms (conforming to IEC 60947-1)
- On-load factor:
- Connections - terminals:
- Screw clamp terminals 1 cable(s) 1…2.5 mm²solid
- Screw clamp terminals 2 cable(s) 1…2.5 mm²solid
- Screw clamp terminals 1 cable(s) 0.75…2.5 mm²flexible without cable end
- Screw clamp terminals 2 cable(s) 0.75…2.5 mm²flexible without cable end
- Screw clamp terminals 1 cable(s) 0.75…1.5 mm²flexible with cable end
- Screw clamp terminals 2 cable(s) 0.75…1.5 mm²flexible with cable end
- Tightening torque: < 1.4 N.m on screw clamp terminals
- Mechanical durability: 30000 cycles
- Quantity per set: Set of 10
- Dimensions:
- Height: 89 mm
- Width: 18 mm
- Depth: 66 mm
- Net weight: 0.105 kg
- Colour: Dark grey